Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0224-00206
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2024 | COT - RSEL - Electrical Final | Re-inspection required | Smoke detectors constantly tripping throughout, half hot receptacle in bedroom 2 not set up to switch, switch controls half hot receptacle in hallway 10/15/24 | |
10/18/2024 | COT - RSEL - Electrical Final | Re-inspection required | Smoke detectors constantly tripping throughout, half hot receptacle in bedroom 2 not set up to switch, switch controls half hot receptacle in hallway 10/15/24 10-18-24, half hot receptacle no power. Bedroom switch controls receptacle in hallway. Missing smoke detector in bedroom 3, add clamp to ac line set,add half hot receptacle to master bedroom, b vent requires a 1 inch clearance, lower thermostat's height to meet include home requirements. |
|
10/21/2024 | COT - RSEL - Electrical Final | Passed | 10-21-24, all items from previous inspection have been corrected. |