Parcel: 141460590


Addresses:

9659 E HARKES DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0224-00199

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
08/01/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing hangers per plan in garage at GLB. Trimmers in pantry call for x2 2x6's. Loose shear wall at pantry marked areas. Provide titans at marked locations. Missing cs16 straps at shear wall south of home. Nailing pattern not per schedule at interior bottom plate. 8/1/2024
08/06/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Applicable 8/6/24: no plans
08/07/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed Exterior and interior walls are properly secured to concrete floor with j-bolts, titan bolts, shot pins, or masa clips. Shear wall plywood sheathing is properly installed and secured to studs with nails per plan requirements. Okay to proceed with rough-in of mechanical, electrical, and plumbing work.