Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2024 |
COT - RSBU - Preslab |
|
Re-inspection required |
10-17-24, reinforcement at hold downs, compaction required throughout, ufer requires 3 inches from earth, top and bottom reinforcement at guest suite #2 not per plans, footing depth not per plans. |
| 10/18/2024 |
COT - RSBU - Preslab |
|
Passed |
10/18/24: Items noted on last inspection are corrected. Okay to pour concrete. |