Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
8/30/24: registers require blocking on three sides, metal housing for exterior lights require wire bushing, multiple circuits tied in together, shower must be under test, pex must have 12" of clearance. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 09/03/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
Add FHA strap behind kitchen hood and nail off every hole. Primary and secondary lines are incomplete. metal housing for exterior lights require wire bushing. Add support for gas line that is laying on pex lines in 2nd bedroom. Secure exhaust duct in 1st bathroom. 9/3/2024 |
| 09/05/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
Corrections were made. 9/5/2024 |