Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0224-00173
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2024 | COT - RSEL - Electrical Final | Re-inspection required | 8/30/24: remove cover from all smoke detectors, Please provide proper ladder for attic access, all thermostat must be placed no higher than 48" o.c, HVAC condenser must have 3" of clearance from grade, electrical whip at condenser must be properly secured, properly insulate refrigerant lines. | |
09/13/2024 | COT - RSEL - Electrical Final | Passed | Corrections were made. 9/13/2024 |