Parcel: 141434000

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-MDP-0224-00173

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
08/30/2024 COT - RSME - Mechanical Final  Re-inspection required 8/30/24: remove cover from all smoke detectors, Please provide proper ladder for attic access, all thermostat must be placed no higher than 48" o.c, HVAC condenser must have 3" of clearance from grade, electrical whip at condenser must be properly secured, properly insulate refrigerant lines.
09/10/2024 COT - RSME - Mechanical Final  Passed Corrections were made. 9/10/2024