Inspection Status: Passed

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0223-00605

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Passed

Date Description Inspector Results Comments
05/22/2024 COT - RSBU - Exterior Clips/Sheathing  Passed Exterior and interior walls are properly secured to concrete floor with cut nails, bolts or a/b bolts. Shear wall hold downs are properly nailed to studs in walls per plan and code. Plywood sheathing on shear walls is properly nailed per plans. Straps are installed and secured to headers of all large openings. Okay to proceed.