Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0223-00588
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2023 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | ||
06/16/2023 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 6/14/23: Multiple Holddowns are over spalled, missing anchor bolts, missing coil strap cs16x5', fire block panels need to be 3/4" min. at dead space, vertical fire block missing at upstairs front wall as well as ceiling, shear wall at second floor needs more nails, sole plate nails not per schedule. 6/16/23: Multiple Holddowns still over spalled, shear wall anchor bolts not per schedule, missing coil strap cs16x5, vertical fire block missing at upstairs front wall as well as ceiling. |
|
06/21/2023 | COT - RSBU - Exterior Clips/Sheathing | Passed |