Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Exterior Clips/SheathingÂ
Permit Number - TC-MDP-0223-00522
Inspection Description - COT - RSBU - Exterior Clips/SheathingÂ
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | Exterior and interior plywood shear walls are properly installed, bolted, and nailed per the plans. All masa clips are properly nailed to bottom plate, all shear wall hold downs are properly nailed to wall studs, and titan bolts are installed were joints in bottom plate happened. Okay to proceed with rough-in of mechanical, electrical, and plumbing. |