Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-MDP-0223-00522
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2024 | RSBU - Building Final | Re-inspection required | 11/6/24: HCS cleanout must have proper cap, All plastic piping on exterior of house must be UV coated, washer pan must terminate with proper fitting at exterior of home. Provide attic access | |
11/08/2024 | RSBU - Building Final | Passed | 11/8/24: Cap has been replaced on HCS clean-out, all plastic pipes have been painted, washer pan drain line has been properly terminated at exterior of house. Okay to issue Certificate of Occupancy. |