Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0223-00481

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/26/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 3x3 plate washers are missing on bolt hold down of sole plate. Headers above doors & windows are not framed to industry standards with the plywood spacers between the 2 by material. Truss clips do not appear to be Simpson H2.5A truss clips.
05/01/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 5-1-23: Plate washers have been placed at each sole plate bolt location. Headers meet the standards for framing. Truss clips are stamped with the Simpson logo. Okay to apply vapor barrier and stucco lathe to the exterior of building.