Inspection Status: Passed
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0223-00416
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2024 | COT - RSEL - Electrical Final | Passed | Construction is completed. Mechanical, electrical, and plumbing fixtures are installed and operational. Electrical panel is properly labeled with AFCI & GFCI breakers installed as required. Exterior lights are installed per plan requirements. Okay to issue Certificate of Occupancy for this permit. | |
08/12/2024 | COT - RSEL - Electrical Final | Re-inspection required | Wrong amperage on A/C Unit. 50 amp installed label on unit says 40 amp maximum. |