Parcel: 14101013E


Addresses:

10025 E LEBARON DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0126-00015

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/03/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 03/03/2026
Missing steel washer plates on SW11 and SW 13, add anchor bolts at marked locations, add cs16 strap to rear patio beam to post. Rear patio on SE side needs fix: SW11 requires not to cut into for pocket beam, requires HUC26-2 hanger instead. NOTE: stopped inspection, upstairs needs to be walked.
03/04/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 03/04/2026
Corrections made to prior inspection. Verified added nails to loose panel and h2.5 at west wall truss to top plate.