Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 14101013E


Addresses:

10025 E LEBARON DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0126-00015

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/03/2026 COT - RSBU - Roof Nailing  Re-inspection required 03/03/2026
Missing steel washer plates on SW11 and SW 13, add anchor bolts at marked locations, add cs16 strap to rear patio beam to post. Rear patio on SE side needs fix: SW11 requires not to cut into for pocket beam, requires HUC26-2 hanger instead. NOTE: stopped inspection, upstairs needs to be walked.
03/04/2026 COT - RSBU - Roof Nailing  Passed 03/04/2026
Corrections made to prior inspection. Verified added nails to loose panel and h2.5 at west wall truss to top plate.