Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0125-00054

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/01/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 5/1/25: Shearwall missing above header at garage option, Anchor bolt at shearwalls not per plan, anchor bolts required where masa clips have only 6 nails installed (7 required), roof nailing was not inspected. Shot pins required 6" from edge and 36" o.c
05/05/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled
05/07/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 5/7/25 corrections made