Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
| Date |
Description |
Inspector |
Results |
Comments |
| 05/01/2025 |
COT - RSBU - Roof Nailing |
|
Re-inspection required |
5/1/25: Shearwall missing above header at garage option, Anchor bolt at shearwalls not per plan, anchor bolts required where masa clips have only 6 nails installed (7 required), roof nailing was not inspected. Shot pins required 6" from edge and 36" o.c |
| 05/05/2025 |
COT - RSBU - Roof Nailing |
|
Canceled |
|
| 05/07/2025 |
COT - RSBU - Roof Nailing |
|
Passed |
5/7/25 corrections made |