Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | At entry stud has to be full height to support headers. Provide Cs16 straps from headers to studs at entry both north and east ends. Nailing at sheathing cannot penetrate more than an 1/8”. Hangers in field are not the same that are called out on plans. Trusses seam to be split due to fastener throughout. Gusset plates are damaged throughout. Provide ladder to verify fasteners to trusses. Add anchor bolts at marked area. Provide truss calcs. Girder trusses missing hardware’s or fasteners. 8/1/2025 |
|
| 08/05/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8.5.25 Engineer letter for splits caused by screws at truss Engineer fix for damaged gussets H25 required at screw to truss where angle cannot be verified |
|
| 09/08/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 9.8.25 Corrections implemented as requested. Ok to proceed. |