Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-MDP-0125-00026

Parcel: 141450470

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
08/01/2025 COT - RSBU - Roof Nailing  Re-inspection required At entry stud has to be full height to support headers. Provide Cs16 straps from headers to studs at entry both north and east ends. Nailing at sheathing cannot penetrate more than an 1/8”.
Hangers in field are not the same that are called out on plans. Trusses seam to be split due to fastener throughout. Gusset plates are damaged throughout. Provide ladder to verify fasteners to trusses. Add anchor bolts at marked area. Provide truss calcs. Girder trusses missing hardware’s or fasteners. 8/1/2025
08/05/2025 COT - RSBU - Roof Nailing  Passed Roof nail approved