Parcel: 141435400


Addresses:

6700 E VIA DE AYATE


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0124-00155

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/26/2024 COT - RSBU - Roof Nailing  Re-inspection required Missing 2x4 studs throughout in garage for girder trusses and posts above, missing 2-2x4 studs at each end for 2-2x8 header between foyer and dining room, missing 2-2x4 for girder truss at dining room, beam to posts not per S5.1 #6, missing second 2x6 stud at exterior by stairs to support GT, blocking between trusses loose not nailed off, roof nailing missing throughout left side of house, rsp4 clips needed at back of house, truss A04 missing proper lateral bracing.
05/02/2024 COT - RSBU - Roof Nailing  Re-inspection required Not ready.
05/06/2024 COT - RSBU - Roof Nailing  Re-inspection required
05/08/2024 COT - RSBU - Roof Nailing  Passed