Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Add shims at gaps between top plate and bottom chord of truss at all middle bearing points with nailed H2.5 clips, missing anchor bolts and shot pins throughout, add toe nailing to stud at laundry. |
| 05/13/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
Missing toe nailing from stud to sole plate at laundry. Marked on sole plate. Correction can be seen at intermediate. Partial-pass. Ok to proceed. |
| 06/21/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|