Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Anchor bolt missing nut at front and back porch, missing anchor bolt at front of garage, fully install shot pins at sole plate behind electrical panel, shear wall at back side of garage missing anchor bolts within 12” of end of sill plate, all headers must be strapped or clipped to studs, missing rsp4 clips by restroom closet, load from Girder Trusses must be carried down continuously. Add studs at first floor and blocking between second and first floor to continue load down to first floor., missing rsp4 clips right side of house at window, all headers must be strapped or clipped to studs. |
| 04/19/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|