Inspection Status: Canceled

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
09/30/2024 COT - RSBU - Interior Shear Bracing  Canceled Canceled by contractor 9/30/2024
10/01/2024 COT - RSBU - Interior Shear Bracing  Re-inspection required Re inspection required. 10/1/2024
10/02/2024 COT - RSBU - Interior Shear Bracing  Not Ready Canceled by contractor 9/30/2024

Re inspection required. 10/1/2024
10/2/24: fasteners not per schedule throughout, shearwalls missing at garage and kitchen, fasteners must be no less than 3/8" from edge and shall penetrate no more than 1/8". Throughout home . Not ready
10/03/2024 COT - RSBU - Interior Shear Bracing  Passed