Inspection History Details
Inspection Status: Passed
Inspection History: RSBU - Building Progress
Permit Number - TC-MDP-0124-00043
Inspection Description - RSBU - Building Progress
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2025 | RSBU - Building Progress | Passed | Construction is completed. Mechanical, electrical, and plumbing fixtures are installed and fully functional. Fire alarms are installed and operational. GFCI & AFCI breakers are installed in panel and where required by code for kitchen, bathroom, laundry room, and exterior outlets. Okay to issue Certificate of Occupancy. | |
| 09/13/2024 | RSBU - Building Progress | Canceled | 9/13/24: canceled per contractor | |
| 10/07/2024 | RSBU - Building Progress | Re-inspection required | 10/7/24: multiple issues in house rips in vapor barrier, DWV not under test. Shower pans and tub not under test. Gas not under test. Stopped inspection. | |
| 10/09/2024 | RSBU - Building Progress | Canceled | 10/9/24: canceled by contractor | |
| 10/14/2024 | RSBU - Building Progress | Re-inspection required | 10/14/24: lath incomplete back of house. rips and penetrations in vapor barrier need to be sealed. shower pan in master not under test. main panel electrical circuits not to plan. | |
| RSBU - Building Progress | Not Ready | corrections not completed. | ||
| 10/23/2024 | RSBU - Building Progress | Canceled | ||
| 11/15/2024 | RSBU - Building Progress | Canceled | 11-15-24, contractor will reschedule |