Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0123-00302
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | Shear wall clips are properly nailed off, H2.5 clips are installed on all trusses and connected to top plate of walls, all exterior walls are properly secured to floor, all exterior shear wall sheathing is properly nailed. Okay to proceed with drying in exterior walls and roof. |