Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Exterior Clips/SheathingÂ
Permit Number - TC-MDP-0123-00302
Inspection Description - COT - RSBU - Exterior Clips/SheathingÂ
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | Shear wall clips are properly nailed off, H2.5 clips are installed on all trusses and connected to top plate of walls, all exterior walls are properly secured to floor, all exterior shear wall sheathing is properly nailed. Okay to proceed with drying in exterior walls and roof. |