Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2024 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
6/21/24: knockouts at panel must be sealed, labeling panel, secure whip at water heater and A/C condenser, receptacle at kitchen no power, B-vent requires 3 screws at joints, B-vent has negative pitch. |
| 06/24/2024 |
COT - RSPL - Plumbing Final |
|
Passed |
Corrections were made. 6/24/2024 |