Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Anchor bolts loose. Tighten all anchor bolts throughout., add nails to hanger at family room, girder truss at kitchen missing 2 2x6 studs and 2 2x4 studs for bearing, missing second balloon framed king stud right side of window by front door, missing rat runs at trusses. |
| 11/14/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Anchor bolts loose. Tighten all anchor bolts throughout., add nails to hanger at family room, girder truss at kitchen missing 2 2x6 studs and 2 2x4 studs for bearing, missing second balloon framed king stud right side of window by front door, missing rat runs at trusses. |
| 11/16/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|
| 11/16/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|