Parcel: 141432350


Addresses:

6766 E VIA OLMEDA


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Excavation/Rebar/Zoning 

Permit Number - TC-MDP-0123-00251

Inspection Description - COT - RSBU - Excavation/Rebar/Zoning 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/07/2023 COT - RSBU - Excavation/Rebar/Zoning  Re-inspection required 7/7/23: clean footings at ufer and by garage, Rebar must have 3" clearance from earth. Footing to left side of kitchen missing rebar reinforcement.