Permit: TC-MDP-0123-00239

Parcel: 141432500


Addresses:

6828 E CAMINO NAIFE

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
04/21/2023 COT - RSBU - Roof NailingĀ  Re-inspection required 4/21/23- missing Anchor Bolts in garage @ front porch, missing hold down on 2x6 exterior garage, need engineer fix for blow out pedestal at rear porch, h25 clips on center bearing wall, too many shiners at roof above stairwell.
06/14/2023 COT - RSBU - Roof NailingĀ  Passed