Parcel: 141434800

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-0123-00220

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/22/2024 RSBU - Building Final  Re-inspection required No water at water hose, refrigerant line at A/C unit must be wrapped in UV rated tape, no ladder for attic access, no plans on site, refrigerator must run on its own circuit, missing plumbing cleanouts per Residential Intermediate inspection, workers in house. House not ready for final. Stopped inspection. More items may be added.
04/23/2024 RSBU - Building Final  Passed