Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/30/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Add nails to masa clips left side of garage, plans call for 2-2x4 studs at GT to support 20” floor GT by stairs, 2x8 joist above stairs has LUS24. Replace and add LUS26 hanger per plans, loose anchor bolts throughout. Tighten all anchors bolts., front porch header not per plans, sister stud holding up 15” GLB at in-law suite kitchen, entry door from garage to in-laws suite calls for 2-2x6 headers, wall at in-laws suite bathroom over spanned, Second floor: studs in wall between master bathroom and Bed. 2 over spanned, back shear wall missing CS16 at each end, add nails to h2.5 clip at bedroom 2, truss A01 missing lateral bracing. |
| 12/08/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Fully install and nail LUS hanger at stairs, loose anchor bolts throughout. Tighten all anchors bolts., back shear wall missing CS16 at each end. |
| 12/28/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|