Permit: TC-COM-1225-02291

Parcel: 130144440


Addresses:

3950 E 22ND ST

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Intermediate

Date Description Inspector Results Comments
05/08/2026 COT - LCEL - Electrical Intermediate Re-inspection required 5-8-26: missing plastic bushings at disconnect box, label all junction boxes above ceiling and at in wall. Provide an updated RFI showing tap box/electrical wall mount at existing dishwashing area. Above ceiling electrical not ready-all junction boxes must be labeled, Mc cabling must be secured and off the ceiling grid, seal open knockouts and provide plastic bushings where awg wires penetrate metal boxes.
05/11/2026 COT - LCEL - Electrical Intermediate Passed Passed 5/11/26