Inspection Status: Partial Pass

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
04/09/2026 COT - LCBU - Framing Partial Pass 4-9-26: add shot pins within 6" (minimum of 2) at the ends of the pony wall sill plate. Will check for correction at intermediates.
05/15/2026 COT - LCBU - Framing Partial Pass 5-15-26: framing approved. Please schedule a drywall screw inspection prior to tape & texture. Install screws 7" o.c. throughout at firewalls.
06/09/2026 COT - LCBU - Framing Passed 6-9-26: okay to tape & texture drywall.