Inspection Status: Not Ready

Inspection History: COT - HCBU - CofO

Permit Number - TC-COM-1222-00294

Inspection Description - COT - HCBU - CofO

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/12/2023 COT - HCBU - CofO Not Ready 10/12/23: called contractor, left message. No one on site.
10/17/2023 COT - HCBU - CofO Re-inspection required 10/12/23: called contractor, left message. No one on site.

10/17/23: center 4 feet of ceiling grid missing at north half of Room 115. Replace all grid and missing ceiling tiles, OR obtain a letter from the Architect of record stating the above is going to be part of a future TI.
10/18/2023 COT - HCBU - CofO Re-inspection required 10/18/23: called contractor, left message. No one on site. Spoke with tenant next door, she stated that they are in the process of moving out and that the area separation wall is to be demolished to create a larger space.
10/19/2023 COT - HCBU - CofO Passed 10/19/23: Contractor has a letter from architect that the missing ceiling tiles are okay because there is a tenant improvement project scheduled to remove a portion of the ceiling to install racks. Okay to issue Certificate of Occupancy.