Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Progress
Permit Number - TC-COM-1222-00264
Inspection Description - COT - HCEL - Electrical Progress
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2025 | COT - HCEL - Electrical Progress | Partial Pass | 2/11/25: electrical underground from light pole north west to south west complete. Remove large rocks from trench. Shading required. | |
| 02/26/2025 | COT - HCEL - Electrical Progress | Partial Pass | 2/11/25: electrical underground from light pole north west to south west complete. Remove large rocks from trench. Shading required. 2/26/25: (1) 1-1/4" conduit from Panel FAHA to pull box on north west corner of existing building. |
|
| 04/30/2025 | COT - HCEL - Electrical Progress | Re-inspection required | 2/11/25: electrical underground from light pole north west to south west complete. Remove large rocks from trench. Shading required. 2/26/25: (1) 1-1/4" conduit from Panel FAHA to pull box on north west corner of existing building. 4/30/25: Receptacles at shooting tower must be GFCI and be WR. Panel schedule must be made up. |
|
| 05/02/2025 | COT - HCEL - Electrical Progress | Partial Pass | 2/11/25: electrical underground from light pole north west to south west complete. Remove large rocks from trench. Shading required. 2/26/25: (1) 1-1/4" conduit from Panel FAHA to pull box on north west corner of existing building. 4/30/25: Receptacles at shooting tower must be GFCI and be WR. Panel schedule must be made up 5/2/25: Corrections made at shooting tower. |
|
| 07/03/2025 | COT - HCEL - Electrical Progress | Passed |