Inspection Status: Partial Pass
Inspection History: COT - CSOL - Electrical Underground Solar Project
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2026 |
COT - CSOL - Electrical Underground Solar Project |
|
Partial Pass |
5-15-26: excavation & reinforcement for 10 drilled pier columns verified per footing depth schedule & S3.0 Detail 101. Okay for concrete placement at progress areas. Electrical conduits to be verified after initial pour. |
| 05/21/2026 |
COT - CSOL - Electrical Underground Solar Project |
|
Partial Pass |
5-21-26: 3-1' schedule 40 EV conduits along court yard, 1-1" light trench near trash enclosure, 1-1 1/2", 9-1" together with 2-2" schedule 40 electrical conduits for EV chargers running north to south along east end of site. Okay to backfill progress areas using shading materials. |
| 08/10/2026 |
COT - CSOL - Electrical Underground Solar Project |
|
Passed |
Passed CLEARANCE DGC |