Inspection Status: Partial Pass

Inspection History: COT - LCBU - Stem Wall/Retaining Wall 

Date Description Inspector Results Comments
04/15/2026 COT - LCBU - Stem Wall/Retaining Wall  Partial Pass Okay to pour the 24" monument wall footer and the other 4 monument 18" wall footers. The 18" wall footers dimensions are modified to work with existing elevations and existing adjacent wall footing conditions. Thicknesses are compensated for so overall the footers will be equivalent or larger than what is designed. Reinforcing is correct with some modifications to allow for existing condition (some verts are epoxy set)- Epoxy set verts and # 5 at 24”Horz are spaced correctly and have good clearances.
Schedule next inspection when the #4 Verts and laps are ready for all walls.
04/27/2026 COT - LCBU - Stem Wall/Retaining Wall  Partial Pass 5 sections for rammed earth monument walls 1, 2, & 3: reinforcement, location, and dimensions are correct, okay to 'pour' and compact.