Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/03/2026 |
COT - LCME - Mechanical Final |
|
Re-inspection required |
1-5-26: called point of contact at 830am-no answer. Arrived on site and spoke with employee who advised that work was performed at subpanel and fixed mini split. Reschedule an inspection, provide a ladder, and plans to verify scope of work. |
| 05/19/2026 |
COT - LCME - Mechanical Final |
|
Re-inspection required |
5-19-26: provide UL listing-mini split missing listing, label disconnect & identify panel/circuit, label breakers at subpanel, install proper bolts with washers at base of mini split and provide approved plans. |