Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
03/19/2025 COT - LCEL - Electrical Underground  Passed All underground electrical is complete
12/16/2024 COT - LCEL - Electrical Underground  Partial Pass 1 1/2" conduit to chlorinator. X2 3/4" from well pump panel. The other is for circuit panel. 1 1/2" is from SEP (station control panel) 1" is for thermostat junction box. 3/4" station control panel. 1 1/2" from flow transmitter to flow meter. 2 spares 1". 2 1/2" from well pump panel to well pad motor. 1" from provisional space. 3/4" from circuit breaker. Conduit for fiber optics x2 1", x1 4", x3 1" to solar field. X2 3" from transformer to new CT can. Okay to backfill progress areas. Shading is required. 12/16/2024










Contact is Angel 520 971 9480