Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1124-02135
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2025 | COT - HCEL - Electrical Underground | Partial Pass | Conduits and ufers for 6 light pole caissons. Ok to place concrete in progress areas. | |
| 08/05/2025 | COT - HCEL - Electrical Underground | Partial Pass | 8-5-25: verified trench depth of 2' on 3/4" schedule 40 electrical parking lot conduits. Total of 15 light pole cassions, 13 will be installed throughout site but 2 will be located near the Autozone parking area and will be scheduled for inspection at a later date. Okay to backfill progress areas. | |
| 08/07/2025 | COT - HCEL - Electrical Underground | Partial Pass | Six light pole bases n North and East sides. | |
| 09/16/2025 | COT - HCEL - Electrical Underground | Partial Pass | Partial pass. Secondaries from transformer to new panel location. (1200 CT can)Total of x4 4” schedule 40. 2 1/2” schedule 40 for new house panel. (Meter) 3/4” for lighting. 2” for future car chargers heading toward broadway. Pending light pole bases near auto zone parking lot area and trash enclosure total of 3. Okay to backfill all progress areas. Shading material is required. 9/16/2025 | |
| 10/28/2025 | COT - HCEL - Electrical Underground | Partial Pass | 10-28-25: verified 1" electrical conduit for caissons. Okay to backfill approximately 300' of open trench located north & east side of site. |