Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Above Ceiling 

Permit Number - TC-COM-1123-02713

Inspection Description - COT - HCBU - Building Above Ceiling 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/02/2024 COT - HCBU - Building Above Ceiling  Re-inspection required Missing supply/return duct at reception and lobby, loose ducts in ceiling, multiple air handlers with openings, mechanical not ready., fire caulk all penetrations going through walls above ceiling, properly support sprinkler system at reception area.
04/11/2024 COT - HCBU - Building Above Ceiling  Passed