Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 04/02/2024 |
COT - HCBU - Building Above Ceiling |
|
Re-inspection required |
Missing supply/return duct at reception and lobby, loose ducts in ceiling, multiple air handlers with openings, mechanical not ready., fire caulk all penetrations going through walls above ceiling, properly support sprinkler system at reception area. |
| 04/11/2024 |
COT - HCBU - Building Above Ceiling |
|
Passed |
|