Inspection Status: Not Ready
Inspection History: COT - HCBU - Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2024 |
COT - HCBU - Framing |
|
Not Ready |
|
| 09/18/2024 |
COT - HCBU - Framing |
|
Partial Pass |
9/18/24: partial for nailing at exterior shear walls |
| 09/24/2024 |
COT - HCBU - Framing |
|
Not Ready |
9/24/24: not ready need fire blocking at interior walls. |
| 09/26/2024 |
COT - HCBU - Framing |
|
Partial Pass |
/26/2025. Partial pass interior fire blocking. |
| 10/09/2024 |
COT - HCBU - Framing |
|
Passed |
10/9/24: Interior walls are properly fire-blocked, all shear wall anchors are installed, and bottom plate bolts are installed with plate washers per plan. Okay to proceed with installation of insulation and drywall. |