Inspection Status: Passed
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2025 |
COT - HCEL - Electrical Intermediate |
|
Passed |
|
| 07/26/2024 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
7/26/24: PARTIAL PASS: 2--4" Electrical conduit through stem wall for secondary service, 2--3" conduits each for 600 amp and 400 amp service panels are installed from main electrical room location to interior electrical room, 2--3" conduits are installed from main electrical room to interior electrical room, and 1--1" conduit is installed from interior electrical room to 5' outside of east wall footing for site lighting. Okay to backfill and compact electrical trenches. |
| 10/21/2024 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
10-21-24: PARTIAL PASS--Electrical wiring is complete in classrooms, hallway, office area, and restrooms. Sub-panels are not installed in interior electrical closet. Okay to insulate exterior walls floor to roof deck. |