Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - HCBU - Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2024 | COT - HCBU - Framing | Not Ready | ||
| 07/23/2024 | COT - HCBU - Framing | Not Ready | ||
| 07/25/2024 | COT - HCBU - Framing | Not Ready | Please make up grounds and neutral buses on split buses on sub panels Require continuous plate on all top and bottom plates Framing missing on fur out wall all top plate needs to be sealed with fire phone register box is still not blocked on three sides on several Places |
|
| 08/02/2024 | COT - HCBU - Framing | Re-inspection required | 8/2/24: DWV not under test, shower pans not under test, foam top plate penetrations. Okay to insulate lids | |
| 08/06/2024 | COT - HCBU - Framing | Passed | Ensure penetrations are fire protected. Ok to insulate and cover walls. |