Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Intermediate
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2024 | COT - HCEL - Electrical Intermediate | Re-inspection required | 9/11/24: copper plumbing in restroom running against sheet metal studs needs to be protected. All top plate penetrations need to be fire foamed. Fur out walls need to be blocked every 10 feet. Registers must be blocked on three sides. Pex going through block wall must have protective sleeve. Stopped inspection | |
| 09/19/2024 | COT - HCEL - Electrical Intermediate | Re-inspection required (with fee) | 1-Fur out walls need to be blocked every 10 feet. 2-copper plumbing in restroom running against sheet metal studs needs to be protected. 3-Complete electrical rough-in. 4- Block below beam saddle is split and displacing; provide fix from EOR. |
|
| COT - HCEL - Electrical Intermediate | Re-inspection required | 9/30/24: metal electrical boxes needed to be grounded. | ||
| 10/04/2024 | COT - HCEL - Electrical Intermediate | Passed |