Parcel: 127040140


Addresses:

4940 E SPEEDWAY BL


Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Above Ceiling 

Permit Number - TC-COM-1122-00065

Inspection Description - COT - HCEL - Electrical Above Ceiling 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/05/2023 COT - HCEL - Electrical Above Ceiling  Re-inspection required 7-5-23: 1-Remove tile to allow inspection. 2-Grid and lights do not match plans.
07/26/2023 COT - HCEL - Electrical Above Ceiling  Re-inspection required 7-5-23: Install landings per Code at back door.
7/26/23: ceiling grid supports exceed 4 feet on center, support MC cable off grid.
07/28/2023 COT - HCEL - Electrical Above Ceiling  Passed