Parcel: 141185990


Addresses:

10041 E OLD VAIL RD


Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Permit Number - TC-COM-1122-00044

Inspection Description - COT - HCEL - Electrical Underground 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
04/25/2025 COT - HCEL - Electrical Underground  Partial Pass 4-25-25, Schedule 40 secondary conduits for transformer verified per plans. Okay to backfill progress areas.
05/15/2025 COT - HCEL - Electrical Underground  Passed
10/11/2024 COT - HCEL - Electrical Underground  Partial Pass Partial Pass--Conduit runs are installed along the east and north sides of building. Okay to shade conduit and backfill trenches.
10/17/2024 COT - HCEL - Electrical Underground  Partial Pass Partial Pass--Conduit runs are installed along the east and north sides of building. Okay to shade conduit and backfill trenches.
10/17/24: conduit runs are installed per plan at North East electrical room and fire riser room,
10/22/2024 COT - HCEL - Electrical Underground  Partial Pass 2/0 Ufer for SES. 2 Ground rods with # 6 ground to SES. 4” conduit for telephone (utilities) schedule 40. Remainder of x9 1” stubbing up into wall in I.T room. Okay to backfill progress areas. 10/22/2024