Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Underground
Permit Number - TC-COM-1122-00044
Inspection Description - COT - HCEL - Electrical Underground
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2025 | COT - HCEL - Electrical Underground | Partial Pass | 4-25-25, Schedule 40 secondary conduits for transformer verified per plans. Okay to backfill progress areas. | |
| 05/15/2025 | COT - HCEL - Electrical Underground | Passed | ||
| 10/11/2024 | COT - HCEL - Electrical Underground | Partial Pass | Partial Pass--Conduit runs are installed along the east and north sides of building. Okay to shade conduit and backfill trenches. | |
| 10/17/2024 | COT - HCEL - Electrical Underground | Partial Pass | Partial Pass--Conduit runs are installed along the east and north sides of building. Okay to shade conduit and backfill trenches. 10/17/24: conduit runs are installed per plan at North East electrical room and fire riser room, |
|
| 10/22/2024 | COT - HCEL - Electrical Underground | Partial Pass | 2/0 Ufer for SES. 2 Ground rods with # 6 ground to SES. 4” conduit for telephone (utilities) schedule 40. Remainder of x9 1” stubbing up into wall in I.T room. Okay to backfill progress areas. 10/22/2024 |