Parcel: 141185990


Addresses:

10041 E OLD VAIL RD


Inspection Status: Partial Pass

Inspection History: COT - HCBU - Framing

Permit Number - TC-COM-1122-00044

Inspection Description - COT - HCBU - Framing

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/03/2025 COT - HCBU - Framing Partial Pass
01/24/2025 COT - HCBU - Framing Passed 1/24/25: Roof decking is properly secured to roof framing. Okay to proceed with roofing application.
12/13/2024 COT - HCBU - Framing Partial Pass Workers are installing steel deck panels for 2nd floor, will be completing steel framing on 1st floor after scaffolding is removed around stairwell.
12/18/2024 COT - HCBU - Framing Re-inspection required Workers are installing steel deck panels for 2nd floor, will be completing steel framing on 1st floor after scaffolding is removed around stairwell.
12/18/24: floor deck shall be attached to each supporting member at 12" o.c at interior bearing and 6" o.c at deck end (not installed per plan at time of inspection), deck support stiffeners per detail 10/S3.1 not installed at time of inspection. Reinforcement not per plan.
12/30/2024 COT - HCBU - Framing Partial Pass 12/30/24: PARTIAL PASS--2nd floor wall framing completed, worker's are screwing off the 3rd floor decking off.