Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCBU - Framing
Permit Number - TC-COM-1122-00044
Inspection Description - COT - HCBU - Framing
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2025 | COT - HCBU - Framing | Partial Pass | ||
| 01/24/2025 | COT - HCBU - Framing | Passed | 1/24/25: Roof decking is properly secured to roof framing. Okay to proceed with roofing application. | |
| 12/13/2024 | COT - HCBU - Framing | Partial Pass | Workers are installing steel deck panels for 2nd floor, will be completing steel framing on 1st floor after scaffolding is removed around stairwell. | |
| 12/18/2024 | COT - HCBU - Framing | Re-inspection required | Workers are installing steel deck panels for 2nd floor, will be completing steel framing on 1st floor after scaffolding is removed around stairwell. 12/18/24: floor deck shall be attached to each supporting member at 12" o.c at interior bearing and 6" o.c at deck end (not installed per plan at time of inspection), deck support stiffeners per detail 10/S3.1 not installed at time of inspection. Reinforcement not per plan. |
|
| 12/30/2024 | COT - HCBU - Framing | Partial Pass | 12/30/24: PARTIAL PASS--2nd floor wall framing completed, worker's are screwing off the 3rd floor decking off. |