Inspection Status: Re-inspection required
Inspection History: COT - HCME - Mechanical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2025 |
COT - HCME - Mechanical Intermediate |
|
Re-inspection required |
Add straps within 8' at spiral and hard duct. Label heat strip option on unit. Secure lines sets. Add 10 mil tape to those that are touching dissimilar metals. Secure line set away from roll up door. Revise all floors. Units are being over amped. Add cool cote coating to line sets on roofs. Secure seal tight whips off of roof. 6/18/2025 |
| 06/30/2025 |
COT - HCME - Mechanical Intermediate |
|
Passed |
|