Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Above Ceiling 

Permit Number - TC-COM-1122-00044

Inspection Description - COT - HCEL - Electrical Above Ceiling 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
04/24/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass 4-24-25, electrical above ceiling verified per plans for riser, electrical, & both elevator machine rooms. Okay to continue with construction at progress areas.
06/17/2025 COT - HCEL - Electrical Above Ceiling  Not Ready Missing deadfront at panel 3rd floor. Add labeling to all panels along with printed panel schedules. Add cover plates to blanks. Label all j boxes. Open j boxes throughout need to be made up and labeled. Mc cable hanging for outdoor signage. Stopped inspection other items may apply. 6/17/2025
06/26/2025 COT - HCEL - Electrical Above Ceiling  Passed 6/26/2025 all corrections have been made.