Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2026 |
COT - LCEL - Electrical Final |
|
Not Ready |
Not ready. Will check all receptacles, smoke detectors and verify panel schedule at sub panel once power has been restored. 10/30/2026 |
| 11/05/2026 |
COT - LCEL - Electrical Final |
|
Not Ready |
Provide GFCI receptacle to all in kitchen areas. Ensure two circuits are provide in kitchen. Bathroom receptacle tied into kitchen circuit must be separate. Exhaust fan not running. Sub panel shall be labeled prior to final. Remove blank cover and add the additional receptacle in bedroom. 11/5/2026 |